ELECTRICAL WIRING REQUIREMENTS FOR ANIMAL CONFINEMENT BUILDINGS BASED ON NATIONAL ELECTRICAL CODE ARTICLE 547 - AGRICULTURAL BUILDINGS |
||||||
BUILDING TYPE |
WIRING METHOD |
LIGHT FIXTURES |
BOXES, FITTINGS, CONTROLS |
MOTORS |
PANEL-BOARDS |
EQUI-POTENTIAL PLANE See note 1 |
Livestock Confinement |
Copper SE, UF, rigid nonmetallic conduit (RNMC) See note 4 |
Enclosed, listed for wet locations. Dusttight and corrosion resistant |
Dusttight, watertight, and corrosion resistant |
Totally enclosed fan cooled (TEFC) |
Not allowed |
Required |
Open-sided building (no gates or doors to confine livestock) |
Copper SE, UF, RNMC |
General use |
General use |
TEFC |
Not allowed |
Required |
Horse barn or stable |
Copper SE, UF, RNMC |
Enclosed over stalls, hay, or bedding. General use elsewhere. See note 2. |
In bedding areas, switches and outlets must be dusttight with weatherproof covers |
TEFC |
General use |
Required |
Milking parlor |
Copper SE, UF, RNMC |
Listed for wet locations |
Watertight and corrosion resistant |
TEFC |
Not allowed |
Required |
Dairy barn, tie stall or stanchion |
Copper SE, UF, RNMC |
Enclosed, listed for wet locations, corrosion resistant |
Dusttight, watertight, and corrosion resistant |
TEFC |
Not allowed |
Required |
Milk room |
Copper SE, UF, RNMC, and EMT with watertight fittings |
Listed for wet locations |
Watertight |
TEFC |
Raintight |
Not required |
Equipment room, office, or lunch room |
General use See note 3 |
General use |
General use |
General use |
General use |
Not required |
Poultry confinement |
Copper SE, UF, RNMC |
Dusttight, watertight, and corrosion resistant See note 5 |
Dusttight, watertight, and corrosion resistant |
TEFC |
Not allowed |
Not required |
Silo and feed rooms |
Copper SE, UF, RNMC |
Listed for damp location, corrosion resistant, dusttight |
Moisture and corrosion resistant, dusttight |
TEFC |
Raintight |
Not required |
Hay or bulk feed storage |
Copper SE, UF, RNMC, and EMT |
Enclosed, dusttight |
Dusttight |
TEFC |
Not allowed |
Not required |
Note 1. An equipotential plane is required to be installed in areas with concrete floors where electrical equipment or systems are installed. A voltage gradient ramp must be installed where livestock regularly enter and exit an area with an equipotential plane.
Note 2. Fixtures over stalls must have substantial guards where mounting does not prevent contact by horses.
Note 3. Only wiring methods approved for the location shall be installed in concealed walls and ceilings of buildings, or portions thereof, that are contiguous with or adjoin confinement areas. (Metallic-sheathed cables, or metallic or nonmetallic raceways may be acceptable) (Nonmetallic-sheathed cables are not permitted)
Note 4. Expansion fittings for rigid nonmetallic conduit (RNMC) shall be installed in accordance with NEC Section 347-9.
Note 5. Keyless gasketed lampholders with brass shells and open lamps are allowed only with special permission. Special permission must be requested and obtained in writing, in advance. Special forms must be completed and approved by the property owner, the owner's insurance company, and the department.
Except for the final service or feeder conductors extended to a building disconnecting means, aluminum conductors, boxes, fixtures, and fittings are not permitted to be installed in any portion of agricultural buildings. Motors must be installed so that dust and debris build-up will not restrict cooling. Thermostats are motor controllers and must be provided with a disconnecting means in accordance with NEC Article 430. All electrical equipment must be readily accessible. Where required, minimum working clearances must be provided. It is advisable to consult with the appropriate insurance company before proceeding with any electrical wiring installation.