| Inquiry: | 96-03 |
| Subject: | Basement Egress Windows |
| Code: |
Code: 1994 UBC Section 310.4 |
| Submitted By: | MN B. O. Uniformity Committee |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | July 22,1996 |
| Question #1: | If I finish my basement into more usable living space, must I
install an egress window even though the space does not include a
bedroom? |
| Answer #1 | The committee will be proposing a code change to clarify that
existing basements are exempt from this requirement. |
| Question #2 | Is a guardrail required on the top of egress window wells that are
adjacent to walkways not used as required exits? |
| Committee comments: | The committee will be proposing a code change to clarify that
existing basements are exempt from this requirement. |
| Answer #2 | No. The building code does not address this particular situation.
(however, see 509.1 for ramps) |
| Committee comments: | Adopted by committee November 8, 1995 and approved (with deletion)
at the 40th Annual Institute of Building Officials on January 12, 1996. |