| Inquiry: | 97-33 |
| Subject: | Exterior landings at stairs |
| Code: |
1994 UBC Section 1004.9 |
| Submitted By: | MN B. O. Uniformity Committee |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | July, 18 1997 |
| Question: | When converting a deck with exterior stairs to an enclosed porch or
room addition, is a landing required on the exterior side of the door at
the top of the stairs? |
| Answer: | Yes "when...exposed to the weather without adequate protection from
a roof, eave, overhang or other covering to prevent moisture or water
accumulation on the surface or at joints between members." |
|
Division comments: |
Yes, unless the only door is simply a screen door or storm
door as permitted in exception 1.3. |
| Committee comments: | Adopted by Committee September 25, 1996 and ratified (as amended) at
the 41st Annual Institute of Building Officials on January 17, 1997.
Modified by the Division. |