Inquiry: |
97-33 |
Subject: |
Exterior landings at stairs |
Code: |
1994 UBC Section 1004.9 |
Submitted By: |
MN B. O. Uniformity Committee |
Approved By: |
Thomas R. Joachim, State Building Official |
Issue Date: |
July, 18 1997 |
Question: |
When converting a deck with exterior stairs to an enclosed porch or room addition, is a landing required on the exterior side of the door at the top of the stairs? |
Answer: |
Yes "when...exposed to the weather without adequate protection from a roof, eave, overhang or other covering to prevent moisture or water accumulation on the surface or at joints between members." |
Division comments: |
Yes, unless the only door is simply a screen door or storm door as permitted in exception 1.3. |
Committee comments: |
Adopted by Committee September 25, 1996 and ratified (as amended) at the 41st Annual Institute of Building Officials on January 17, 1997. Modified by the Division. |