Inquiry: |
98-47 |
Subject: |
Exemption to school sprinkler requirement |
Code: |
1996 MSBC 1305.0904 subp. 1. |
Submitted By: |
MN B. O. Uniformity Committee |
Approved By: |
Thomas R. Joachim, State Building Official |
Issue Date: |
August 3, 1998 |
Question: |
When does MSBC 1305.0904 subp. 1 exempt an E-1 school occupancy from the requirement for a sprinkler system? |
Answer: |
When E-1 occupancies or mixed occupancy buildings containing E-1 occupancies do not exceed 20,000 square feet, or are otherwise separated into areas not exceeding 20,000 square feet by area separation walls or occupancy separations of not less than a two hour fire-resistive rating. Adopted by committee November 20, 1997 and ratified at the 42nd Annual Institute of Building Officials on January 16, 1998. |
Committee comments: |
Adopted by committee November 20, 1997 and ratified at the 42nd Annual Institute of Building Officials on January 16, 1998. (Modified by Division) |