| Inquiry: | 98-47 |
| Subject: | Exemption to school sprinkler requirement |
| Code: |
1996 MSBC 1305.0904 subp. 1. |
| Submitted By: | MN B. O. Uniformity Committee |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | August 3, 1998 |
| Question: | When does MSBC 1305.0904 subp. 1 exempt an E-1 school occupancy from
the requirement for a sprinkler system? |
| Answer: |
When E-1 occupancies or mixed occupancy buildings containing E-1 occupancies do not exceed 20,000 square feet, or are otherwise separated into areas not exceeding 20,000 square feet by area separation walls or occupancy separations of not less than a two hour fire-resistive rating. Adopted by committee November 20, 1997 and ratified at the 42nd
Annual Institute of Building Officials on January 16, 1998. |
|
Committee comments: |
Adopted by committee November 20, 1997 and ratified at the 42nd Annual Institute of Building Officials on January 16, 1998. (Modified by Division) |