Inquiry: |
96-05 |
Subject: |
Sleeping room window replacements |
Code: |
Code: 1994 UBC Sections 310.4 and 3403 |
Submitted By: |
MN B. O. Uniformity Committee |
Approved By: |
Thomas R. Joachim, State Building Official |
Issue Date: |
July 22,1996 |
Situation #1: |
The entire window unit is removed and a new window unit is installed. |
Answer: |
Compliance with U.B.C. Sec. 310.4 is required. |
Situation #2: |
A building is moved into or within the jurisdiction. The sleeping rooms do not comply with Sec. 310.4. |
Answer #2: |
(Same as answer #1) UBC Sec. 3404 requires that "buildings or structures moved into or within the jurisdiction shall comply with the provisions of this code for new buildings or structures." |
Division comments: |
Division Comments: UBC Section 104.2.7 permits modifications in code enforcement where there are "practical difficulties." This may be considered in both situations particularly if the house was built under a previous code that may have allowed a 48 inch sill height or 5.0 square feet in openable area. |
Committee comments: |
Adopted by committee November 8, 1995 and approved (with deletion) at the 40th Annual Institute of Building Officials on January 12, 1996. |