Inquiry: |
98-43 |
Subject: |
Fasteners for fire-resistive construction |
Code: |
1994 UBC Table 7-B |
Submitted By: |
MN B. O. Uniformity Committee |
Approved By: |
Thomas R. Joachim, State Building Official |
Issue Date: |
August 3, 1998 |
Question: |
Are pneumatic roofing nails approved for nailing a single ply of gypsum sheathing on a fire-resistive wall? |
Answer: |
No. However, if other types of fasteners are proposed having an evaluation report that permits their use in a specific assembly, then they could be accepted as an alternate approved material. |
Committee comments: |
Footnote 1 of Table 7-B permits staples as fasteners only for those designs in Table 7-B. This footnote does not apply to the designs found in the Gypsum Association's Fire-Resistance Design Manual. Adopted by committee November 20, 1997 and ratified at the 42nd Annual Institute of Building Officials on January 16, 1998. |