| Inquiry: | 99-04 |
| Subject: | Clear floor space at water closets |
| Code: |
1999 MSBC 1341.0448, Subpart 2 |
| Submitted By: | Building Codes and Standards Division |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | May 3, 1999 |
| Question: | Can a lavatory or other permanent fixture or obstruction encroach
into the clear floor space shown in Figure 28 for an accessible water
closet? |
| Answer: |
No. "Clear floor space" is defined in 1341.0350, Subpart 19 as
unobstructed space which, unless otherwise stated, extends from the
floor to a height of 80 inches above the floor. |
| Division comments: | Requirements specific to clear floor space for water closets in
dwelling units is covered in 1341.1640, Item E, Subitem (2).
Approved by the Building Codes and Standards Interpretation Committee |