| Inquiry: | 99-02 |
| Subject: | Primary function area/existing single-use toilet room |
| Code: |
1999 MSBC 1341.0411, Subpart 2 |
| Submitted By: | MN B. O. Uniformity Committee |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | May 3, 1999 |
| Question: | When updating existing single-use toilet rooms is required due to
the alteration of a primary function area, when can the existing toilet
facilities be considered acceptable? |
| Answer: | An existing single-use toilet room may be considered adequate when:
a) a turning space complying 1341.0420, Subpart 3 is provided within the
room; b) the water closet is centered 18 inches from the side wall; c)
there is at least 18 inches from the center line of the water closet to
the leading edge of the nearest fixture or obstruction; and, d) there is
a minimum of 36 inches of clear floor space directly in front of the
water closet. All other toilet room facilities and elements such as door
swing clearance, fixture heights and clearances, and grab bar location
must be code compliant. Existing single-use toilet rooms meeting these
requirements may be considered as meeting UBC section 104.2.8 for
alternate design.
Approved by the Building Codes |