| Inquiry: | 97-26A |
| Subject: | Primary function area/existing single-use restroom(s) |
| Code: |
1994 UBC Appendix Section 1111.1.2 |
| Submitted By: | Building Codes and Standards Division |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | February 24, 1997 |
| Question: | When updating existing toilet facilities is triggered by the
alteration of an area of primary function, when can existing single-use
restrooms be considered adequate? |
| Answer: | If: a) clear floor space is provided complying with CABO/ANSI A117.1
section 4.2.3; b) the water closet is centered 18 inches from the side
wall; c) there is at least 18 inches from the center line of the water
closet to the leading edge of the nearest fixture, and; d) there is a
minimum of 36 inches of clear floor space directly in front of the water
closet, the room size may be considered to meet UBC section 104.2.8 for
alternate design. All other restroom facilities and elements, e.g., door
swing clearance, fixture heights, grab bars, etc., must be code
compliant.
Approved by Building Codes and Standards Access Committee January 9 ,1997. |