Opinion: Location of required toilet facilities

Inquiry: 

96-15

Subject: 

Location of required toilet facilities

Code:

1994 UBC Sections 1105.2.2 and 1103.2.2

Submitted By:

Yeater, Hennings, Ruff, Shultz, Rokke, Welch Architects

Approved By:

Thomas R. Joachim, State Building Official

Issue Date: 

October 14, 1996

Question:  

According to Section 4.9.3 are all stairs required to either have nosings or sloped risers?

Answer #1:

May the only required accessible toilet rooms be located on a floor without elevator or ramp access when such vertical access is not required by UBC 1103.2.2?
 

Answer #2:

Although UBC Chapter 11 does not address locating required accessible toilet rooms on a floor not provided with vertical access, it was the division's original intent that required accessible toilet rooms be located on an accessible route.

Division comments:

This is consistent with the ADA Accessibility Guidelines as they require accessible toilet rooms to be on an accessible route (4.13).

Approved by Building Codes and Standards Access Committee September 26, 1996.