| Inquiry: | 97-41A |
| Subject: | Guest room design standards |
| Code: |
1996 MSBC 1340.1103 Subpart 5 |
| Submitted By: | MN B. O. Uniformity Committee |
| Approved By: | Thomas R. Joachim, State Building Official |
| Issue Date: | June 9, 1997 |
| Question: | Should accessible rooms in occupancies specified in MSBC 1340.1103
Subpart 5 (hotel, motel and similar occupancies), be designed to meet
general CABO/ANSI technical standards or the design requirements for
accessible dwelling units. |
| Answer: | Accessible rooms required in MSBC 1340.1103 Subpart 5 must meet the
same design standards as other public and common use areas as described
in the general CABO/ANSI technical standards. |
|
Committee comments: |
The technical design standards for accessible dwelling units of
CABO/ANSI section 4.33 are intended for those occupancies specified in
MSBC 1340.1103 Subpart 4 only. These occupancies are permanent housing
type dwelling units intended for extended residency and are not subject
to routine turnover by the general public as are hotel/motel guest rooms
or other types of transient housing. Because the type of occupancies
specified in MSBC 1340.1103 Subpart 5 are intended for short, temporary
stays, they must be designed to meet the general design standards of
CABO/ANSI.
Approved by Building Codes and Standards |