| Inquiry: | 07-02 |
| Subject: | Group S Occupancy |
| Code Reference: |
2006 IBC Section 1104.4, Exception 2 |
| Submitted by: | CCLD |
| Prepared by: | Curt Wiehle, Building Code Representative |
| Approved by: | Thomas Anderson, State Building Official |
| Issue Date: | August 22, 2007 |
| Question: |
Does 1104.4, Exception 2 apply to all Group S occupancies? |
| Answer: |
A discussion with ICC has resulted in a different interpretation and
application of the 2006 IBC Section 1104.4, Exception 2 than was
previously understood and presented at several Accessibility Code
seminars. The prior interpretation expressed at the code seminars was
that Exception 2 gave a general exception for the provision of an
accessible route to mezzanines and stories in all Group S occupancies.
According to ICC, the intent of Exception 2 is that it only applies to
the spaces and areas in the referenced Sections 1107 and 1108. The only
area of a Group S occupancy addressed in Section 1108 is self-service
storage facilities. Therefore, Section 1104.4, Exception 2 only applies
to self-service storage facilities and no other type of Group S
occupancy. Other uses within the Group S classification are subject to
Section 1104.4, Exception 1, as amended at Minnesota Rules, 1341.0011
Subp. 4 A. |