Water-heating boiler inspection
Boiler checks are recommended by
ASME Code Section IV and
adopted by the state of Minnesota
Note: Note: Log these checks. These boiler checks are recommended as
a minimum and are not all inclusive. Additional checks may need to be made
depending on the type, size, previous maintenance history, age and condition of
the plant. All plants should be operated in a safe, prudent and attentive
manner.
Daily:
- Observe operating pressures and temperatures
- Observe general conditions
- Determine cause of unusual noise or conditions
- Record in log
Weekly:
- Observe condition of flame
- Check fuel-oil supply
- Observe operation of circulating pumps
Monthly:
- Safety relief valve lift lever test
- Test flame detection devices
- Test limit controls
- Test operating controls
- Inspect fuel supply systems
- Test low-water cut off
Every five years:
- Internal inspection after cleaning